System earthings and incidents on MV side that result in LV disturbances

Low voltage networks, unless a replacement uninterruptible power supply (with galvanic insulation) or a LV/LV transformer is used, are influenced by MV. This influence takes the form of: capacitive coupling, galvanic coupling and common... Read more
By EEE, ADBU

Three abnormal situations leading to an uncontrolled release of SF6 gas

This technical article deals with the assessment of risk to personnel in the case of an abnormal situation leading to an uncontrolled release of SF6 gas into the atmosphere. Generally , such... Read more
By EEE, ADBU

Line to Line Fault Definition, Fault Current Calculation

What is Meant by Line to Line Fault ?

When two conductors of a 3 phase system are short circuited line to line fault or unsymmetrical fault occurs.This fault is severe compared to symmetrical faults in power system.In order to safeguard power system network analysis of unsymmetrical faults (in this case line to line fault) must be done.

Fault Current Calculation in Line to Line Fault

Consider a 3-phase system with an earthed neutral.Assume a line-to-line fault between the blue (B) and yellow (Y) lines as shown in figure The conditions created by this fault lead to :


Again taking R-phase as the reference, we have,



June 27, 2017 at 12:27AM by EEE, ADBU

2 types of synchronisers required on a power system with two supplies

Synchronisers are required at points on a power system where two supplies (either generator and grid, or two grid supplies) may need to be paralleled. They are more than just a measuring... Read more
By EEE, ADBU

What is Bridge Rectifier? Operation, Circuit Diagram, Advantages, Disadvantages, Applications



June 24, 2017 at 10:24PM by EEE, ADBU

Why we use only 11KV / 22KV / 33KV / 66KV / 110KV / 230KV / 440KV. Why can’t we use other voltage like 54KV / 89KV etc?

Why electricity is being transmitted in multiple of 11?


Have you ever wondered? why we use only 11KV / 22KV / 33KV / 66KV / 110KV / 230KV / 440KV which are multiples of 1.11(we can say multiple of 11).We can generate this voltages efficiently because of form factor of sine wave is 1.11.So it is efficient to produce that range of voltages.Form factor is the ratio of RMS value to average value.For a pure sine wave it is around 1.11.
We can't have a combination of other then a multiple of 1.11.
So we can see all the voltages are made inevitably multiple of this value (1.1, which is the form factor of ac wave).Also it provides us the best economic construction of step up and step down transformers.

Right Answer:The answer given above is taken standard electrical book.But that is wrong the actual answer is when we want to maintain 10KV at receiving end, transmission companies transfer 10% extra than receiving end voltage.i.e., 11KV simillary 10% of 20/30/60/100KV gives us 11KV / 22KV / 33KV / 66KV / 110KV respectively.
These questions sounds same :

Searches related to why voltages are multiples of 11
why generation voltage is 11kv
why the substation voltages are multiple of 11kv
why transmission line 11kv or 33kv 66kv
why do we use ac and not dc system in india?
maximum generating voltage in world
what is 11kv electrical system
generation voltage of power plant
generating voltage levels

June 24, 2017 at 06:46PM by EEE, ADBU

Difference between Squirrel Cage and Slip Ring Induction Motor

Why functional specification of SCADA project is essential for its success

Well documenting the SCADA system requirements is probably the single most significant contributor to the success of a SCADA project. It may seem obvious but let’s say it anyway: writing the Functional... Read more
By EEE, ADBU

How to Draw Potier Triangle/ZPF characteristics ?

Regulation by Zero Power Factor ( ZPF) method  of Alternator:

During the operation of the alternator, resistance voltage drop IaRa and armature leakage reactance drop IaXL are actually emf quantities and the armature reaction reactance is a mmf quantity. To determine the regulation of the alternator by this method OCC, SCC and ZPF test details and characteristics are required.

-As explained earlier OC and SC tests are conducted and OCC and SCC are drawn.

-ZPF test is conducted by connecting the alternator to ZPF load and exciting the alternator in such way that the alternator supplies the rated current at rated voltage running at rated speed.
-To plot ZPF characteristics only two points are required. One point is corresponding to the zero voltage and rated current that can be obtained from scc and the other at rated voltage and rated current under zpf load.
-This zero power factor curve appears like OCC but shifted by a factor IXL vertically and horizontally by armature reaction mmf as shown below in figure. 



Following are the steps to draw ZPF characteristics:

-By suitable tests plot OCC and SCC. Draw air gap line. Conduct ZPF test at full load for rated voltage and fix the point B.

-Draw the line BH with length equal to field current required to produce full load
current on short circuit..
-Draw HD parallel to the air gap line so as to cut the OCC. Draw DE perpendicular to HB or parallel to voltage axis.
-Now, DE represents voltage drop IXL and BE represents the field current required to overcome the effect of armature reaction.
-Triangle BDE is called Potier triangle and XL is the Potier reactance. Find E from V, IRa, IXL and .
-Use the expression E =√ (V cos  Ã˜+ IRa)² + (V sin ) + IXL)² to compute E. Find field current corresponding to E. Draw FG with magnitude equal to BE at angle (90+ ) from field current axis, where is the phase angle of current from voltage vector E (internal phase angle).
-The resultant field current is given by OG. Mark this length on field current axis. From OCC find the corresponding E0. Find the regulation.



June 22, 2017 at 02:58AM by EEE, ADBU

Auto Transformer Principle of Operation,Working & Applications

An auto transformer is a electrical transformer having only single winding which acts as both primary and secondary,so in input and output connected to shared single winding.

Why we need to go for Auto Transformer ?

We have some advantages of auto-transformer over normal two winding transformer.
1.Auto transformers usually smaller in size,because one winding is eliminated.
2.as size is small cost also low(so cheap in cost)
3.as the winding is same so leakage reactance will be less.
4.increased kVA rating.

Auto Transformer

Construction, Principle of Operation Of Auto Transformer: 

In Auto Transformer, one single winding is shared as primary winding as well as secondary winding.as in transformer copper wire wound on silicon steel.as shown in the figure input connected at fixed positions.but on other side we employ some tapping to get variable output voltages.Variable turns ratio at secondary can be obtained by changing the tappings of the winding.

Auto Transformer

Copper Savings in Auto Transformer:

If we compare conventional two winding transformer and  auto transformer the amount of copper needed for auto transformer is less.weight of copper of any winding depends upon its length and cross - sectional area.and length depends on no.of turns,cross - sectional area varies with rated current.

Auto Transformer

copper in the section AC proportional to, 

(N1-N2)I1

weight of copper in the section BC proportional to

(I1-I2)N2

Hence, total weight of copper in the winding of auto transformer proportional to,



In similar way it can be proved, the weight of copper in two winding transformer is proportional to,


N1I1+N2I2
=2N1I1(Since, in a transformer N1I1=N2I2)

Let's assume, Wa and Wtw are weight of copper in auto transformer and two winding transformer respectively,



∴ Saving of copper in auto transformer compared to two winding transformer,
∴ Wtw -Wa=kWtw 


June 22, 2017 at 02:32AM by EEE, ADBU