Lead Lag Compensation In Control System

LEAD LAG COMPENSATION IN CONTROL SYSTEM

In this post we are going to learn about types of compensations, why compensation of control system is required, lead and lag compensation in control system.

Series Compensation:

If we connect compensation circuit between plant and error detector it is called series compensation. The circuit for series compensation is as follows.

Parallel compensation:

If we connect compensation circuit as feedback type it is called parallel compensation. The circuit for parallel compensation is as follows.

Load compensation:

If we combine series and parallel feedback circuits it results in Load compensation. The circuit for load compensation is as follows.

Why compensation of control system is required?

1.We do compensation for a control system in order to achieve best performance.

2. To make an unstable system stable.

3. It increases steady state accuracy of the system.

4. Reduces overshoot of a system.

5. Generally compensation is done in the form of feed forward path gain adjustment.

6. When we apply compensation network to a control system it introduces poles and zeros in to the system which results in change of transfer function, this makes the performance of the system to alter.

Note: Increase in the steady state accuracy brings instability to the system.

Phase Lead Compensation:

A lead network has one pole and one zero, zero must be near to the origin and also the poles and zeros must lie on the negative real axis. By seeing the pole zero plot of lead compensation network you can get a clear idea, its figure is shown below.

Pole Zero Plot Of Lead Compensation Network :


So to add a dominating zero( zero near to origin) to a control system we use phase lead compensation network. The network is shown below.

Phase Lead Compensation Network:


From this circuit we have,

Now on equating above two I values we get,

Determining Transfer Function Of Lead Compensation Network:

Here transfer function is the ratio of output voltage to input voltage. 

By applying Laplace transform on both sides of above equation we get,

we know,

By substituting this equation in the above equation we get transfer function,


Here T and ɑ are time constant and attenuation constant respectively.



This lead network when connected in series gives positive phase angle to the system which makes the zero to be close to origin .

Substitute s = j𝛚 in the transfer function , also we have ɑ < 1 then we get transfer function as,
In order to know at what frequency we get maximum phase lead we need to differentiate the above equation and equate to zero. Now we get,
Here θm is the maximum phase lead angle, corresponding magnitude of the transfer function at maximum θm is 1/a.

Advantages Of Phase Lead Compensation:

1. As the gain crossover frequency shifts to a higher value because of phase lead compensation the speed of the system increases.

2. Maximum overshoot of the system decreases because of phase lead compensation.

Disadvantages Of Phase Lead Compensation:

No improvement in steady state error. 

Effects Of Phase Lead Compensation:

1. Increase in phase margin.

2. Faster Response.

3. Increase in velocity constant Kv.

4.The slope of the magnitude plot reduces at the gain crossover frequency so that relative stability improves and error decrease due to error is directly proportional to the slope.

Phase Lag Compensation:

A lag network has one zero and one pole, pole must be near to the origin and also the poles and zeros must lie on the negative real axis. By seeing the pole zero plot of lag compensation network you can get a clear idea, its figure is shown below.

Pole Zero Plot Of Lag Compensation Network :

So to add a dominating pole(pole near to origin)to a control system we use phase lag compensation network. The network is shown below.



From this circuit we have,

Determining Transfer Function Of Lag Compensation Network:

Here transfer function is the ratio of output voltage to input voltage. 

By applying Laplace transform on both sides of above equation we get,

By substituting

 in above equation. we get transfer function.


here T and β are respectively the time constant and DC gain.
In the lag compensator pole is more dominating than the zero and because of this lag network introduces negative phase angle to the system when connected in series.

Substitute s = j𝛚 in the transfer function , also we have ɑ < 1 then we get transfer function as,
In order to know at what frequency we get maximum phase lead we need to differentiate the above equation and equate to zero. Now we get,

Where, θm is the maximum phase lead angle.β is generally chosen to be greater than 10.


Advantages Of Phase Lag Compensation:

1.Low and high frequencies can be attenuated.

2. Increase in steady state accuracy.

Disadvantages Of Phase Lag Compensation:

Decrease in speed of system.

Effects Of Phase Lag Compensation:

1. Increase in phase margin.

2. Decrease in bandwidth.

3. Increase in gain cross over frequency.

4.Response will be slower before due to decreasing bandwidth, the rise time and the settling time become larger.

Phase Lag Lead Compensation:

By cascading both lead and lag networks we can obtain the benefits of both lead network and lag network which makes the given system to work better. Given below is circuit diagram of lead lag network.

Circuit Diagram Of Lead Lag Network:


Determining Transfer Function Of lead lag compensation network:

Here transfer function is the ratio of output voltage to input voltage. 

By applying Laplace transform on both sides of above equation we get,
By substituting,


in above equation we get,

Pole Zero Plot Of Lead Lag Network:

In the lag-lead compensation pole is more dominating than the zero and because of this lag-lead network may introduces positive phase angle to the system when connected in series.

Advantages Of Phase Lead Lag Compensation:

1. Improved accuracy.

2. Speed of the system increases because it shifts gain crossover frequency to a higher value.
In this way Lead Lag compensation networks are used in order to increase the performance of a system.

In this post we have learnt about lag lead compensators in control system.

To download this post on lag lead compensators in control system as Pdf click here.






June 14, 2017 at 11:05PM by EEE, ADBU

4 most popular PLC programming languages for implementation of control diagrams

PLCs from different manufacturers can be programmed in various ways. Popular programming languages for PLCs are ladder diagrams, Function Block Diagrams (FBD), and statement list. With a few exceptions, a program written... Read more
By EEE, ADBU

Single Phase Induction Type Energy Meter Working, Construction, Creeping, Compensation etc.

Single Phase Induction Type Energy Meter Construction,Working Principle,Operation,Creeping,Torque Equation

The measurement of energy is the same process as measurement of power except that the instrument not merely indicates the power or rate of supply of energy but must take into account also the length of time for which the rate of energy is continued. There are basically three types of energy meters.
(a) Electrolytic meters
(b) Motor meters
(c) Clock meters.
Out of the above, motor meters are very widely used and among motor meters also induction type watt-hour meters are more commonly used and will be dealt with here. Single phase induction type energy meter working explained including constructional details.
READ HERE : PMMC Working & Operation

Single Phase Induction Type Energy Meter Construction

The construction of this meter is more or less similar to induction type watt-meter. The main alterations are the provision of only one pressure coil upon the central limb of the shunt magnet and only one copper shading band upon this limb. In addition there are two copper bands placed obliquely on the other two limbs of this magnet, their objective is to provide compensation against friction error in the energy meter (see figure).

In this meter the moving system is allowed to revolve continuously instead of being allowed merely to rotate through a fraction of one revolution as in an indicating instrument. The speed of revolution is proportional to the power in the circuit. It follows, therefore, that the no. of revolutions made by the revolving system in any given time is proportional to the energy supplied. The number of revolutions made by the meter is recorded by a counting mechanism consisting of a train of wheels to which the spindle of the rotating system is geared.

Single Phase Induction Type Energy Meter Working

The control of speed is brought about by a permanent magnet called the brake magnet.The magnet is placed opposite to the electromagnet used for providing deflecting torque and it induces currents in the disc which produces retarding torque proportional to their magnitude which latter is proportional to the speed of the rotating system. This system attains a steady speed when the retarding torque exactly balances the driving torque produced by the power in the circuit. The braking torque produced by the brake magnet depends upon the strength of the magnet.

Torque Equation:

If  φ is the flux of the brake magnet, i the current induced by the rotation of the moving system in the field of the brake magnet and TB is the braking torque, then
TB  ∝ i.φ
If n is the speed of the rotating system (disc) and e the voltage induced in the disc of the meter.
e ∝ n.φ
Let r be the resistance to the path of eddy current i in the disc, hence i = e/r.
and  TB  ∝ φ.(e/r)
∝ φ².(n/r)

This braking torque equals the constant driving torque TD when a steady speed of the disc
is attained. Thus if N be the steady speed of the meter

T'B  ∝ φ².(N/r)
and at balance T'B = TD ∝ φ².(N/r)  or N  ∝ (r/φ²).TD

Hence the steady speed attained by the meter for a constant driving torque TD is directly proportional to the resistance of the path of the induced eddy currents and inversely proportional to the square of the flux of the brake magnet. Therefore, it can be seen that it is very important for brake magnet to have constant magnetic strength throughout the use of the energy meter. It is to be noted that the spring control and pointer of the watt-meter have been replaced in the energy meter by a brake magnet which provides braking torque as explained above.

Using the theory of induction watt-meter.
Operating or driving torque ∝ VI cosφ
where V is the supply voltage across the shunt coil and ! the load current through the series coil of the meter and φ the p.f. angle between V and I.
Now the braking torque has been shown to be proportional to the speed N of the disc i.e.
TB ∝ N
Since for a steady speed N, the driving torque TD is equal to TB, we have N ∝ VI cosφ or power is proportional to speed N.Thus the total no. of revolutions which equals ∫N.dt is proportional to ∫VI cosφ dt   i.e. proportional to energy supplied.

The speed of the disc can be adjusted by suitably positioning the brake magnet with respect
to the spindle of the disc. If the brake magnet is moved towards the spindle the braking torque
decreases and if taken away from the spindle the braking torque increases.
An energy meter is rated in terms of the supply voltage, the full load current and number
of revolutions of the disc per kWhr (also known as constant of the energy meter). These are
marked on the dial of the energy meter.

What is creeping in energy meter?

Creep:In some meters a slow but continuous rotation of the disc is obtained when the pressure coils are energized and there is no load current passing through the current coil i.e. current coil is not energized. This may be due to incorrect friction compensation to vibration, to stray magnetic field or to the fact that the supply voltage is in excess of the normal voltage.

To prevent such creeping of the meter two holes or slots are cut in the disc on opposite sides of the spindle. The disc tends to remain stationary when one of the holes comes under one of the poles of the shunt magnet. In some cases a small piece of iron wire is attached to the edge of the disc. The force of attraction of the brake magnet upon this iron wire is sufficient to prevent the creeping of the disc under no load condition.

Friction Compensation In Energy Meter:
The two shading bands embrace the flux contained in the two outer limbs of the shunt magnet and thus eddy currents are induced in them which cause a phase displacement between the enclosed flux and the main gap flux. As a result a small driving torque is exerted on the disc, this torque being adjusted by variation of the position of these bands to compensate for friction torque in the instrument.
The friction compensation can be checked whether it is correct or not by connecting light load under which condition it should run at the correct speed.

Energy Meter Phase Angle Error:
It is desired that the phase angle between the applied voltage to the pressure coil and the shunt magnet flux should be at 90° which is adjusted with the help of shading band on the shunt magnet. An error due to incorrect adjustment of the position of this shading band will be evident when the meter is tested on a load whose p.f. is less than unity. An error on the "fast" side under these conditions can he eliminated hy bringing the shading hand further drawn the limb of the shunt magnet i.e. nearer to the disc.

June 11, 2017 at 12:16AM by EEE, ADBU

Basic Electronics (MCQs With Explanatory Answers)

Basic Electronics (MCQs With Explanatory Answers)

Basic Electronics (MCQs With Explanatory Answers)Q1. Choose the below option in terms of ascending order of band gap energy

Options

  1. Diamond, Graphite, Silicon
  2. Graphite, Silicon, Diamond
  3. Silicon, Graphite, Diamond
  4. Silicon, Diamond, Graphite

Show Explanatory Answer

Show Explanatory Answer

Answer: 2.  Graphite, Silicon, Diamond

Explanatory Answer:

Diamond has the highest bandgap energy, about 6eV. It is this high bandgap which separates the filled valance band from the conduction band and makes Diamond an insulator. Though Graphite is also a form of Carbon, like Diamond, its crystal symmetry is different and band gap energy is about 1eV, making it a conductor. Bandgap energy of Silicon is about 1.21eV, which can be acquired only with increase in temperature, making it a semiconductor.

Q2. Band gap Energy for Silicon and Germanium at Room Temperature (300°K) are ____ & ____ respectively: –

  1. 56eV, 1.1eV
  2. 72eV, 1.2eV
  3. 1eV, 0.72eV
  4. 1eV, 0.56eV

Show Explanatory Answer

Show Explanatory Answer

Answer: 3.  1eV, 0.72eV

Explanatory Answer

Below are the band gap energy relations with temperature for both Silicon and Germanium

Egsi (T) = 1.21 – 3.60 x 10-4

Egge (T) = 0.785 – 2.23 x 10-4

Substituting T = 300 in both the above equations, we get Bandgap energies as given below;

Egsi (300) = 1.1 eV

Egge (300) = 0.72 eV

Q3. Electrical characteristics of a semiconductor depends on concentration of free electrons and holes.

  1. True
  2. False

Show Explanatory Answer

Show Explanatory Answer

Answer: 1. True

Explanation:

Current Density in any conducting material is given as:

 J=( nµn + pµp ) eE= σE

Where, n = concentration of electrons, p  = concentration of holes, e = charge, E = applied electric field, and σ = conductivity.

Thus it can be seen that the electrical characteristics depends on concentration of electrons and holes. Thus, the above statement is true.

Q4. Transport of charge carriers in semiconductor is achieved through: –

  1. Conduction and Diffusion
  2. Conduction
  3. Diffusion
  4. None of the above

Show Explanatory Answer

Show Explanatory Answer

Answer: 1. Conduction and Diffusion

Explanatory Answer:

Two ways in which charge carriers are transferred in semiconductor are – conduction and diffusion

Conduction in semiconductor is accomplished by movement of free electrons and holes. While electrons are negative charge carrying particles, holes are positive charge carrying particles. Both their current is in same direction.

Diffusion is caused by movement of charge carriers from higher concentration area to lower concentration area. This is possible because of non-uniform concentration in semiconductors.

Q5. The electron mobility of Germanium at room temperature (in Kelvins), for an electron diffusion constant of 99 is approximately: –

  1. 3200 cm2/V-sec
  2. 4500 cm2/V-sec
  3. 3800 cm2/V-sec
  4. 2000 cm2/V-sec

Show Explanatory Answer

Show Explanatory Answer

Answer: 3. 3800 cm2/V-sec

Explanatory Answer:

As per Einstein’s equation for diffusion,Einstein’s equation for diffusion - basic electronics mcqs with explanatory answers

Where, Dn = Electron Diffusion Constant, DP = Hole Diffusion Constant, µp = Hole Mobility, µn  = Electron Mobility and VT = Volt equivalent of temperature, = T/11600.

At room temperature, i.e. T = 300°K, VT = 0.0258 V approx

Substituting Dn = 99 and VT = 0.025 in the above equation, we get µn  = 3837.20 or 3800 approx.

Q6. Carrier lifetime for holes and electrons in a semiconductor ranges from –

  1. Milliseconds to hundreds of nanoseconds
  2. Microseconds to seconds
  3. Nanoseconds to hundreds of microseconds
  4. Nanoseconds to thousands of milliseconds

Show Explanatory Answer

Show Explanatory Answer

Answer: 3. Nanoseconds to hundreds of microseconds

Explanation: For an intrinsic semiconductor with equal concentration of holes and currents, the carrier lifetime for free electrons and holes is determined by the rate of recombination. While new electron-hole pairs are formed due to thermal agitation, existing electron-hole pair disappear due to recombination.

Q7. Which metal among these is widely used as a recombination agent by semiconductor manufacturers to obtain desired carrier lifetime of charge carriers?

  1. Silver
  2. Gold
  3. Iron
  4. Aluminum

Show Explanatory Answer

Show Explanatory Answer

Answer: 2. Gold

Explanation: Addition of metallic impurities in the semiconductor introduces new energy states in the forbidden gap of the semiconductor crystal, thus increasing the level of recombination.

Q8. The Hall effect is used to determine the

  1. Only the carrier concentration of semiconductors
  2. Current flowing across a semiconductor
  3. Type of semiconductor and carrier concentration
  4. None of the above

Show Explanatory Answer

Show Explanatory Answer

Answer: 3. Type of semiconductor and carrier concentration

Hall effect is the phenomenon of induction of electric field in a semiconductor specimen carrying current of magnitude I, when placed in a transverse magnetic field, B. If current is in positive X direction, Magnetic field is in positive Z direction, force will be exerted in negative Y direction. The polarity of voltage, VH across the specimen determines whether it is N-type or P-type.

Also, carrier concentration is determined as:

n (p) = ρ/e, where ρ = charge density and e is magnitude of charge

Now, ρ = 1/RH,, where RH is Hall coefficient and is given as: RH = VHw/BI

w = width of the specimen in direction of magnetic field.

Q9: The thickness of space charge region for a P-N junction diode is of the order of :-

  1. 10-4 cm
  2. 10-2 cm
  3. 10 cm
  4. 100 cm

Show Explanatory Answer

Show Explanatory Answer

Answer: 1. 10-4 cm

Explanatory Answer:

For a P-N junction diode, the space charge region is the region devoid of mobile charge carriers near to the junction. The electro-static potential variation in this region forms a potential barrier which opposes further diffusion of opposite charge carriers across the junction.

Q10. Formation of a junction between a sample of P-type and N-type material causes _______ action

  1. Rectifying
  2. Conducting
  3. Insulating
  4. None of the above

Show Explanatory Answer

Show Explanatory Answer

Answer: 1. Rectifying

Explanatory Answer: Addition of donor atoms into one side of an intrinsic semiconductor (like Germanium) and acceptor atoms into another side, causes formation of a junction. Under no external applied electric field, a potential barrier exists across the junction due to formation of depletion region (depletion of mobile charge carriers). However, when an external electric field is applied such that p-region is of positive polarity and n-region is of negative polarity, the potential barrier is reduced, causing flow of current. This is called Forward biasing.

When the opposite occurs, i.e. p-region is of negative polarity and n-region is of positive polarity, the potential barrier is increased, hindering the flow of current. Thus,  since the p-n junction device would allow flow of electricity in only one half of the electric signal, but not in the other half, this constitutes rectifying action.

Q 11. Cut-In or breakdown voltage of Silicon diode is greater than that of Germanium diode because ______.

  1. Reverse saturation current in a Silicon diode is lesser than that in Germanium diode
  2. Reverse saturation current in Germanium diode is lesser than that in Silicon diode
  3. The current is initially less dependent on voltage for a Silicon diode
  4. None of the above

Show Explanatory Answer

Show Explanatory Answer

Answer: Options (1) and (3)

Explanatory answer: For a Germanium diode, the breakdown voltage is about 0.2 V, whereas that of Silicon diode is 0.6 Volts. The reason being that, reverse saturation current in a Ge diode is about 1000 times more than that in Si diode. Also, current flowing through the diode is as given below;

I = Io ( e V/ηVT  – 1 )

For Ge, the symbol  η = 1, whereas that for Si is 2 for small currents and 1 for large currents. Hence, for first several tenths of volts, the current varies as e V/2VT.

Q 12. For intrinsic Germanium, the change in conductivity per degree rise in temperature is: –

  1. Increases approximately by 6%
  2. Decrease approximately by 8%
  3. Increases approximately by 5%
  4. Remains unchanged

Show Explanatory Answer

Show Explanatory Answer

Answer: 1. Increases approximately by 6%

Explanatory answer: Intrinsic concentration for any semiconductor is as given below;

ni2 = Ao T3 e -EGO  / kT) 

Conductivity of intrinsic Germanium varies with concentration as given below;

σ = ni (µn+ µp ) e

Substituting the constant values for intrinsic Germanium and merging both the above equations, we get that conductivity increases by approximately 6% per degree rise in temperature.

Read More Here : Electrical & Electronics Engineering MCQS with Explanatory Answers

The post Basic Electronics (MCQs With Explanatory Answers) appeared first on Electrical Technology.



June 09, 2017 at 06:50AM

Did you test your electrician’s skills recently? Take the quiz. It’s time!

It’s always a good idea to put the sparks into your memory and shed light on things you have learned years ago. Whether you are a rookie in a field of electrical... Read more
By EEE, ADBU

3 earthing fault typologies and connection of the CB poles in a DC network

In order to break a short-circuit current in a d.c. system, it is necessary to connect the CB poles in a suitable way. To carry out this operation, it is necessary to... Read more
By EEE, ADBU

Low voltage ride through in grid connected hybrid renewable energy systems

Researches so far shows that, by 2020, around 20% of the total energy production worldwide will be generated from renewable energy. But the major problem with the standalone system is that the... Read more
By EEE, ADBU

Department of EEE organizes NCERS-2016 jointly with Civil Engineering Department

A two day National Conference on Environmental Remote Sensing (NCERS) was held at the School of Technology on 13-14 December 2016. NCERS-2016, organized by Department of Electrical and Electronics Engineering and Department of Civil Engineering, was co-sponsored by Indian Space Research Organization (ISRO), Department of Space (Govt. of India).

The conference was inaugurated by the Chief Guest, Shri PLN Raju, Director, North Eastern Space Applications Centre. Prof. Arup Kumar Sarma, IIT Guwahati was the guest of honour for the inaugural session and Dr. Sameer Saran, Scientist SF, Indian Institute of Remote Sensing delivered the keynote address. Fr Stephan Mavely, Vice-Chancellor, Assam Don Bosco University(ADBU) extended his heartfelt gratitude to all the resource persons, participating researchers, students and organizers for making this attempt of holding a National Conference on remote sensing application as remote sensing technology has not yet been utilized extensively in-spite of having enormous scope for North East India.

Group Photo

The inaugural ceremony was presided over by Prof Manoranjan Kalita, Director, School of Technology. In his speech he urged to create awareness among the upcoming student community and researchers by showcasing the potential of remote sensing in resolving the core issues of the subjects of Geo-informatics.

In the two day technical session of the conference the resource persons were Prof. Parag Phukon, Head of Geological Sciences, Gauhati University, Prof. Subashis Dutta, Head of Civil Engineering, IIT Guwahati, Prof. Anup Sakia, Head of Geography, Gauhati University and Dr. Dhrubajyoti Sahariah, Dept. of Geography, Gauhati University. They delivered invited talks on various aspects of environmental remote sensing. The conference was attended by more than 70 participants and 21 technical papers on various topics supported by remote sensing such engineering, geography, geology, environment, hydrology and meteorology were presented.

Remote sensing is the data capturing tool of Geo-informatics which is described as electronics sensing of the object or phenomena at a known time without being physical contact with the object. The basic advantage of remote sensing is that data are spatial in nature and devoid of human subjectivity.

Participants in the conference




Mr. Bikramjit Goswami, Organizing Secretary, NCERS-2016

12 installation tips for implementing a good residual protection

All installations have an earth leakage current that is mainly due to the conductor’s capacitive leakage and to anti-parasitic or EMI filtering capacitors, for example class I equipment. The sum of these... Read more
By EEE, ADBU

Setting of overload, Short circuit & Ground Fault Protection of MCCB (PART-2)

(2) For Short Circuit Protection (Magnetic Setting):

  (C) Short Time pickup Current Setting (Im):

  • Short time protection is time-independent.
  • It is determines or sets the level of fault current at which the short-time trip delay countdown is actuated.
  • Short Time Pick up Value (Im) (multiplied by the ampere rating) sets the short circuit current level at which the circuit breaker will trip after the set time delay.
  • The short-time pickup (Isd) sets current level (below instantaneous trip level) at which circuit breaker will trip after the preset time delay.
  • Standard Practice for Setting:
  • No trip for a current below 80% of the short time setting
  • Trip for a current equal to 120% of the short time setting
  • The trip time is Less than 0.2 s for a short time protection with no time delay and equal to the value of the time delay tsd for a protection with time delay

(D) Short time delay Setting ™:

  • Short Time delay sets the amount of time the breaker will carry both a low level and high fault currents before tripping.
  • tm sets length of time the circuit breaker will carry a short circuit within the short-time pickup range.
  • Delays bands are labeled in seconds of short-circuit current at 10 times the ampere rating.
  • The short time delay can be set to I2t On and I2t OFF settings (Inverse Time Delay).
  • (A) I2t OFF: Gives Constant time delay usually in multiplication of 0.5 sec. It has not inverse-time delay Characteristic. It is used for coordination with other circuit breakers with electronic trip devices and for coordination with thermal-magnetic circuit breakers.
  • (B) I2t ON :Gives an inverse-time delay that resembles the time/current characteristics of fuse It is used for coordination with fuses and upstream transformer

(3) For Instantaneous Trip (Short Circuit Protection):

(E) Instantaneous Pickup Setting (Ii):

  • Instantaneous protection is time-independent.
  • It is determines the level of fault current that will actuate a trip with no time delay.
  • Ii value (multiplied by the ampere rating (In)) sets the short-circuit current level at which the circuit breaker will trip with no intentional time delay.
  • This protection trips to eliminate quickly high value currents and its trip times cannot be set
  • The instantaneous function will override the short-time function if the instantaneous Pickup is adjusted at the same or lower setting than the Short Time Pickup.
  • Standard Practice for Setting:
  • No trip for a current below 80% of the instantaneous setting
  • Trip for a current equal to 120% of the instantaneous setting
  • The trip time is less than 0.2 second.

 (4) For Ground Fault Protection:

(F) Ground Fault Pickup Setting (Ig):

  • It is determines the level of fault current at which the ground fault trip delay countdown is actuated.

(G) Ground Fault Delay Setting (Itg) :

  • It is determines the amount of time the breaker will carry a ground fault before tripping.
  • It can be set to I2t On and I2t OFF settings.
  • (A) I2t Response:I2t Out ,For coordination with other circuit breakers with electronic trip devices and for coordination with thermal-magnetic circuit breakers.
  • (B) I2t Response: I2t In ,For coordination with fuses and upstream transformer

 Example for Settings of MCCB for Protections

Example1: We have Sub feeder MCCB Size of 2000A, Short Circuit Current is 4000A. Maximum Load Current is 1000A .What is Over current (Long Time) and Short Circuit (Short Time) and Instantaneous setting of MCCB.

  • Here In=2000A

Over current Setting:

  • Dial Setting=(Load current / MCB Rating) =1000/2000=0.5 , set Dial at 0.5
  • Over current Setting Ir=0.5xIn =0.5X2000=1000A
  • For Set Over Current Time Delay: It is necessary to overview Over current Time delay of downstream MCCB and Upper stream MCCB for better coordination otherwise for downstream fault upper stream MCCB gives tripping.
  • Downstream Over current Time Delay< Over current Time Delay< Upper stream Over current Time Delay.
  • In Our example it is last MCCB in circuit and upper stream MCCB Over current delay setting is 2 Sec so Select tr=1 Sec.

Short Circuit Current Setting:

  • Dial Setting=( Short Circuit Current/ MCB Rating) =4000/2000=2
  • Short Circuit Setting Isd=2xIn=2×2000=4000A
  • Downstream Short current Time Delay< Short  current Time Delay < Upper stream Over current Time Delay Short  current Time Delay
  • Our example it is last MCCB in circuit and upper stream MCCB Short Circuit current delay setting is 0.4 Sec so Select Isd=0.2Sec.
  • For coordination of other MCCB we need I2t ON with 0.2 Sec delay.

Instantaneous Tripping Setting:

  • Instantaneous Tripping gives instant tripping without any delay for switching or short Circuit current.
  • Instantaneous Tripping >= Short Circuit Tripping Setting
  • If We can set Ii=3xIn =3×2000=6000A , It will full fill our requirement
  • Here Ii>Isd=6000A>4000A.

 




June 01, 2017 at 06:18PM