By EEE, ADBU
School of Technology, Assam Don Bosco University (tinyurl.com/eee-adbu)
How to calculate number of steps & reactive power of the capacitor banks
By EEE, ADBU
Auto-reclose schemes for re-energising the line after a fault trip
By EEE, ADBU
Current sensors as the eyes of RCD and tips for their correct installation
By EEE, ADBU
Applications of Synchronous Motors || Advantages/Disadvantages
In our electrical edition already we have discussed synchronous motor working principle ,why synchronous motor is not self starting? etc.The most important thing is why mostly we use synchronous motors over induction motors.Here we have the reasons..!
Synchronous motor always runs at constant synchronous speed irrespective of the load and variable power factor operation. As seen earlier its power factor can be controlled by controlling its excitation. For over-excitation its power factor is leading in nature, which is very important from the power factor correction point of view.
Applications of Synchronous Motors
We use synchronous motors where we need almost constant speed in the operation.So applications of synchronous motors list goes like this, we use them in,
- Machine tools,
- Motor generator sets,
- Synchronous clocks,
- Stroboscopic devices,
- Timing devices,
- Belt driven reciprocating compressors,
- Fans and blowers,
- Centrifugal pumps,
- Vacuum pumps,
- Pulp grinders,
- Textile mills,
- Paper mills line shafts,
- Rolling mills,
- Cement mills etc.
Some more uses of synchronous motors:
Not only for the above purposes we also use synchronous motors for power factor correction.You might have known about synchronous condenser[If not read here].Also used as phase advancers and phase modifiers for voltage regulation of the transmission lines. This is possible because the excitation of the synchronous motor can be adjusted as per the requirement.
Disadvantages of synchronous motor :
The disadvantages of synchronous motor are their higher cost, necessity of frequent maintenance and a need of d.c. excitation source, auxiliary device or additional winding provision to make it self starting. Overall their initial cost is very high.
May 10, 2017 at 07:09PM by EEE, ADBU
How to recognize harmonics symptoms – What to look for and where to look?
By EEE, ADBU
Setting of overload, Short circuit & Ground Fault Protection of MCCB (PART-1)
Introduction:
- There are various types of protections setting in MCCB, which define various protection of Electrical Network.
- In MCCB we can set most of protection are adjustable according to Electrical Load profile.
- The main adjustable Setting in MCCB are
- Over current Setting
- Short Circuit Setting
- Ground Fault Setting
Meaning of each selector switches of MCCB
- As Per Standard IEC 60947-2 defines the names of the selector switches.
| Setting | Adjustment | Protection For |
| Ir | Long time Pick up Current Setting (or thermal Setting). This is a multiplication coefficient of the rating of the device. (Ir=xIn) | Protection against overloads |
| tr | Long time delay Setting in seconds, enabling in particular the starting current of a motor to be tolerated. (tr=Sec) | Protection against overloads |
| Im / Isd | Short time (Magnetic Setting). This is a multiplier of the Ir setting, often 1.5 to 10 times the Ir current (im=xIr) | Protection against short circuits. |
| tm / tsd | Short time delay Setting, enabling in particular the discrimination (time) to be increased with downstream feeders and the magnetization peaks of a transformer or a motor to be tolerated. It is recommended that the I²t selector switch is set to the ON position.(tm=Sec) | Protection against short circuits. |
| Ii | Instantaneous current Setting. Protecting the installation against strong short circuits (dead short circuits) by instantaneous tripping without Time Delay and self-protection of the circuit breaker.
The Ii > Isd. |
Protection against Dead Short circuits. |
| Ig | for monitoring the earth fault current circulating in the Phase and Earth conductor in TNS systems | Earth protection |
| tg | Earth protection time delay | Earth protection |
| I delta n | Adjustment of the sensitivity of the earth leakage protection | Earth leakage protection |
| delta t | Earth leakage protection delay. | Earth leakage protection |
Setting of each Protection switch of MCCB
(1) For Low level Fault / Over Current Protection (Thermal Setting):
(A) Long-Pickup Current Setting (Ir):
- It is determines the continuous ampere rating of the breaker.
- Long time protection is time-dependent.
- Long Pickup (Ir) value (multiplied by the ampere rating (In) of MCCB) sets the maximum current level which the circuit breaker will carry continuously.
- If MCB is 1000A Rating but Full Load current is 800A than MCCB Rating can be changed from 1000A to 800A by setting it 0.8, Now Ir=0.8XIn =0.8×1000=800Amp
- If the current exceeds this value for longer than the circuit breaker will trip at the set delay time.
- Long time protection is inverse time type (with I2t constant)
- The long-time pickup (Ir) is adjustable from 4 to 1.0 times the sensor plug rating (In)
- Standard Practice for Setting:
- No trip for a current below 105% of Ir
- Trip in less than two hours for a current equal to for
- 120% of Ir for an electronic trip unit and for
- 130% of Ir for a thermal-magnetic trip unit
- For a higher fault current, the trip time is inversely proportional to the fault current value.
(B) Long-Time delay Setting (tr):
- Long time delay (tr) sets length of time that the circuit breaker will carry a sustained overload before tripping.
- The delay bands are labeled in seconds of over current at six times the ampere rating.
- Long-time delay is an inverse time characteristic in that the tripping time decreases as the current increases.
- The long-time delay (tr) sets the length of the time that the circuit breaker will carry an over current (below the short-time or instantaneous pickup current level) before tripping.
- The Long time delay can be set to I2t On and I2t OFF settings.
- (A) I2t Response:I2t Out ,For coordination with other circuit breakers with electronic trip devices and for coordination with thermal-magnetic circuit breakers.
- (B) I2t Response: I2t In ,For coordination with fuses and upstream transformer
May 09, 2017 at 11:08AM
Sizing calculations for 20/3.3 kV, 12.5 MVA transformer feeder cable
By EEE, ADBU
Dangerous magnetic field exposure near transformer substation in the building
By EEE, ADBU
The attached rod technique – reliable and handy ground testing method
By EEE, ADBU
Protection of capacitor banks by fuses (during energization and operation)
By EEE, ADBU